Sign In | Join Free | My himfr.com |
|
Ask Lasest Price | |
Brand Name : | Ruixiang |
Model Number : | RX-40HP |
Certification : | ISO9001/CE |
Price : | RMB 6500-800000/PC |
Delivery Time : | 15-20 Units |
Payment Terms : | T/T |
Supply Ability : | 500days |
Air Cooled Low Temperature Chiller 40HP Low Temperature Glycol Chillers
Glycol chillers are industrial refrigeration systems that use for
glyco mixed with water for anti-freezing, to lower the freezing
point of the circulation water in the cooling system.
Low temperature glycol chiller is a kind of water cooling
equipment, it can provide a constant temperature, constant current,
constant pressure of a cooling equipment. The glycol chiller water
is between 0℃ and -40℃ and the chilled water will be transported to
the equipment or products that need cooling through chiller pump.
Air-cooled glyco chiller is built-in insulation water tank and
water pump, no need to add another cooling tower to heat. It is
very easy to install and move. But it has high requirements on the
working environment. It is cooled by hot air circulation, so if the
ventilation effect of the installation workshop is not good, it
will directly affect the refrigeration effect of the chiller.
Application
Industrial glycol water chiller unit is used to cool the hot parts
of the equipment, so that the equipment can work normally at low
temperature. Used in Beverage filling, spindle cooling, CNC machine
tools, grinding miller, reaction system, welding machine, cutting
machine and other equipment, temperature adjustment range can be 40
degrees below zero.
Specification
Model | AW-40L | |
nominal cooling capacity | kcal/h | 21323 |
at -25 ℃ | kw | 24.80 |
input power | kw | 34 |
power supply | 3PH~380V 50HZ | |
refrigerant | type | R404a |
type of control | expansion valve | |
compressor | type | hermetic scroll(piston) |
power(kw) | 30 | |
condenser | type | Shell and tube |
chilled fluid flow (m3/h) | 28.7 | |
inlet and outlet pipe diameter (inch) | 2-1/2 | |
evaporator | type | Plate heat exchanger |
chilled fluid flow (m3/h) | 11.98 | |
inlet and outlet pipe diameter (inch) | 2-1/2 | |
pump | power (kw) | 4 |
lift(m) | 20 | |
safety protection | compressor over temperature, over current, high and low pressure, over temperature, flow switch, phase sequence, phase-missing, exhaust overheating, anti-freezing | |
dimension | mm | 2400*1100*1980 |
weight | kg | 1600 |
The nominal cooling capacity is according to: Inlet chilled fluid
temperature: -20℃,supply chilled fluid temperature: -25℃
Features of glycol chiller cooling system
The proportion of Ethylene Glycol Aqueous Solution of glycol water
chiller unit
Operating temperature | Concentration | Density | Specific heat capacity | Heat conductivity | Viscosity | Freezing point |
℃ | % | ×10³ Kg/m³ | KJ/(kg.k) | W/m.k | Pa.s | ℃ |
0 | 25 | 1.03 | 3.834 | 0.511 | 3.8 | -10.6 |
-10 | 35 | 1.063 | 3.561 | 0.4726 | 7.3 | -17.8 |
-20 | 45 | 1.08 | 3.312 | 0.441 | 21 | -26.6 |
-30 | 55 | 1.097 | 2.975 | 0.3725 | 90 | -41.6 |
![]() |